Before purchasing CFI-I prep torrent, you can log in to our website for free download. During your installation, CFI-I exam torrent hired dedicated experts to provide you with free online guidance. During your studies, CFI-I exam torrent also provides you with free online services for 24 hours, regardless of where and when you are, as long as an email, we will solve all the problems for you. At the same time, if you fail to pass the exam after you have purchased CFI-I prep torrent, you just need to submit your transcript to our customer service staff and you will receive a full refund.
Topic | Details |
---|---|
Topic 1 |
|
Topic 2 |
|
Topic 3 |
|
Topic 4 |
|
As old saying goes, no pains, no gains. You must depend on yourself to acquire what you want. No one can substitute you with the process. Of course, life has shortcut, which can ensure you have a bright future. Our CFI-I study materials will become your new hope. If you are ambitious and diligent, our study materials will lead you to the correct road. Thousands of people have regain hopes for their life after accepting the guidance of our CFI-I Study Materials. You should never regret for the past.
NEW QUESTION # 84
After conducting the annual test of a dry barrel hydrant, what is the maximum length of time permitted for full drainage to take place?
Answer: C
Explanation:
Dry barrel hydrants must be tested annually to ensure proper drainage and operation. According to NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems:
After testing, full drainage of the hydrant must occur within 15 minutes. This ensures no residual water remains in the hydrant barrel, which could freeze in cold climates and damage the hydrant.
If the hydrant fails to drain within 15 minutes, it indicates an obstruction or malfunction in the drainage system that must be corrected.
10 minutes (A): Not enough time for standard drainage.
30 minutes (C) and 60 minutes (D): Exceed the acceptable limit defined by NFPA 25.
Reference:
NFPA 25, Section 7.3.2: Annual testing and drainage requirements for dry barrel hydrants.
NEW QUESTION # 85
What is the maximum travel distance to a fire extinguisher with a 20-B rating for an ordinary (moderate) type hazard?
Answer: C
Explanation:
The travel distance to fire extinguishers for different hazard classifications is governed by NFPA 10, Standard for Portable Fire Extinguishers.
For ordinary (moderate) hazards, such as those involving moderate quantities of flammable liquids or combustibles, the maximum travel distance to a fire extinguisher with a 20-B rating is 50 feet (15.25 meters).
The B rating refers to extinguishers effective against Class B fires, which involve flammable liquids (e.g., oils, gasoline, solvents).
The 50-foot requirement ensures that fire extinguishers are accessible within a reasonable distance to promptly respond to a fire.
30 feet (A) applies to higher hazard levels like kitchens or specific severe risks.
75 feet (C) is more typical for Class A hazards.
100 feet (D) would not meet NFPA 10 standards for moderate hazards involving flammable liquids.
Reference:
NFPA 10, Section 6.2.1.1: Travel distance requirements based on hazard classification.
NEW QUESTION # 86
Where shall fire department connections on wet-pipe automatic sprinkler systems be located?
Answer: A
Explanation:
The placement of the fire department connection (FDC) for a wet-pipe automatic sprinkler system is governed by NFPA 13, Standard for the Installation of Sprinkler Systems.
The FDC must be located on the system side of the water supply check valve (A). This ensures that the fire department can pump water into the system effectively and directly supply the sprinkler system during an emergency.
Suction side of booster pumps (B): This placement would not supply water correctly to the system during firefighting operations.
Supply side of the check valve (C): This would prevent water from entering the sprinkler system since the check valve blocks backflow from the FDC.
Above the dry-pipe valve (D): This applies to dry-pipe systems, not wet-pipe systems.
Reference:
NFPA 13, Section 8.17.2.4: Location requirements for fire department connections.
NEW QUESTION # 87
Underground and exposed piping shall be flow tested to determine the internal condition of the piping at what minimal interval?
Answer: C
Explanation:
Comprehensive and Detailed Step-by-Step Explanation:
Flow Testing for Piping:
According to NFPA 25 (Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems), Section 14.2.1, underground and exposed piping must be flow tested at least once every 5 years.
This ensures the internal condition of the piping is adequate and free from obstructions, corrosion, or deposits that could affect water flow.
Why Every 5 Years is Required:
Over time, buildup or deterioration within the piping can restrict water flow, impacting the performance of the fire protection system.
Regular testing helps identify and address issues before they compromise fire safety.
Other Options Explained:
Option B (Every 6 years), Option C (Every 10 years), Option D (Every 20 years): These intervals do not meet the minimum requirements established in NFPA 25.
Summary:
Flow testing of underground and exposed piping must be conducted once every 5 years to ensure their internal condition meets fire protection standards.
NEW QUESTION # 88
The appropriateness of the safeguards required by the Life Safety Code to individual buildings and structures bears due regard to all EXCEPT which of the following?
Answer: A
Explanation:
The Life Safety Code (NFPA 101) ensures that fire and life safety safeguards are appropriate to the risks posed by a building or occupancy. Key considerations include:
Fire load of the occupancy (B): The quantity and combustibility of materials influence fire severity and spread.
Number of persons exposed (C): Occupant load determines evacuation requirements and system capacities.
Capabilities of the occupants (D): Includes factors like mobility, age, and ability to respond to emergencies.
The age of the building (A) is not a primary factor under the Life Safety Code. Safeguards apply regardless of a building's age, as older buildings may still require updates to meet current safety standards.
Reference:
NFPA 101, Section 4.6.6: Considerations for applying safeguards in buildings and structures
NEW QUESTION # 89
......
The NFPA CFI-I certification exam offers a great opportunity to advance your career. With the Certified Fire Inspector I (CFI-1) certification exam beginners and experienced professionals can demonstrate their expertise and knowledge. After passing the Certified Fire Inspector I (CFI-1) (CFI-I) exam you can stand out in a crowded job market. The Certified Fire Inspector I (CFI-1) (CFI-I) certification exam shows that you have taken the time and effort to learn the necessary skills and have met the standards in the market.